FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
918-520b
MODELS: P33-NG4 Natural Gas P33-LP4 Propane
10/31/11
WARNING:
If the information in these instructions are not followed exactly,
a re or explosion may result causing property damage,
personal injury or loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other ammable vapors and
liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a quali ed
installer, service agency or the gas supplier.
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any appliance
Do not touch any electrical switch:
do not use any phone in your
building.
Immediately call your gas supplier
from a neighbour's phone. Follow
the gas supplier's instructions.
If you cannot reach your gas
supplier, call the re department.
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
www.regency- re.com
Owners &
Installation Manual
P33-4 Zero Clearance
Direct Vent Gas Fireplace
Vue de la page 0
1 2 3 4 5 6 ... 63 64

Résumé du contenu

Page 1 - Direct Vent Gas Fireplace

FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4918-520bMODELS: P33-NG4 Natural Gas P33-LP4 Propane10/

Page 2

10Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONCaution RequirementsThe top, back and sides of the fi replace are defi ned by stand

Page 3

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace11INSTALLATIONCOMBUSTIBLE MANTELSBecause of the extreme heat this fi replace emits, the mantel c

Page 4 - TABLE OF CONTENTS

12Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONMANTEL LEG CLEARANCES WITH CONTEMPORARY FACEPLATECombustible mantel leg clearance

Page 5 - SAFETY LABEL

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace13INSTALLATION3) For exterior walls, insulate the enclosure to the same degree as the rest of

Page 6 - REQUIREMENTS

14Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONGHIIMJLKPQON10" (254mm)dia. Hole throughwall Vent.Opening for gasconnectionT

Page 7

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace15INSTALLATIONNote: When constructing the framed opening, please ensure there is access to ins

Page 8

16Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONThe Top Facing Support, the Side Nailing Strips and the 2 Top Standoffs must be c

Page 9

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace17INSTALLATIONEXTERIOR VENT TERMINATION LOCATIONSMinimum Clearance RequirementsCanada1USA2AClea

Page 10 - INSTALLATION

18Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONWherever necessary due to external location of cap, the AstroCap can be replaced

Page 11

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace19INSTALLATIONTermination CapWall Thimble 2 pieces(10" (254mm) Outer Diameter)2”x4”or2”x6”

Page 12

2Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceTo the New Owner:Congratulations! You are the owner of a state-of-the-art Gas Fireplace by FP

Page 13

20Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONRIGID PIPE VENTING SYSTEMSHorizontal or Vertical TerminationsThe minimum componen

Page 14

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace21INSTALLATION4” X 6-5/8” RIGID PIPE CROSS REFERENCE CHARTComponents from different Manufacture

Page 15

22Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONDescriptionSimpsonDirect Vent Pro®SelkirkDirect Temp™American MetalProducts®Ameri

Page 16

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace23INSTALLATION• Vent must be supported at offsets.• Firestops are required at each fl oor le

Page 17

24Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONThe P33-4 is approved for a maximum 40 ft. straight vertical, with rigid pipe ven

Page 18

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace25INSTALLATIONRIGID PIPE VENTING ARRANGEMENTS Horizontal TerminationsREGENCY® DIRECT VENT SYST

Page 19

26Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONHorizontal Venting with Two (2) 90o ElbowsHorizontal Venting with Three (3) 90o E

Page 20

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace27INSTALLATIONHorizontal Venting with Three (3) 90o ElbowsVertical Venting with Two (2) 90o Elb

Page 21

28Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONVertical Venting with Three (3) 90o ElbowsVertical Venting with Three (3) 90o Elb

Page 22

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace29INSTALLATIONFlex LinerExhaustFlueA maximumof two certifiedjoiner kitsmay be usedper length.#9

Page 23

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace3INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALEThis Regency® product has been teste

Page 24

30Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONVENTING ARRANGEMENTS - VERTICAL TERMINATIONS with Co-linear Flex System for bothR

Page 25

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace31INSTALLATIONRiser VentTerminationMin. 6-1/4"*(159mm)Diagram 3UNIT INSTALLATION WITH HORI

Page 26

32Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONGAS LINE INSTALLATIONThe gas line is brought through the right side of the applia

Page 27

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace33INSTALLATIONGAS PIPE PRESSURE TESTINGThe appliance must be isolated from the gas supply pipin

Page 28

34Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONEach Kit contains one LPG Conversion Kit and one DCSparker Kit.LPG Conversion Kit

Page 29

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace35INSTALLATIONWARNING!Do not overtighten the screw. Recommended to grip7) Turn control knob to

Page 30

36Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATION4) Connect the DC spark generator wires to the SIT Valve with the screw, which i

Page 31

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace37INSTALLATIONNote: The logs must not be in the unit.3) Insert the back brick panel by careful

Page 32

38Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONDiagram 1Diagram 3STANDARD FLUSH DOORThe standard fl ush door comes with a black f

Page 33

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace39INSTALLATIONOPTIONAL BAY DOORThe Bay louvers MUST be usedwith the Bay glass option.The option

Page 34

4Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace4TABLE OF CONTENTSOptional Bay Door ... 39Op

Page 35

40Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATION6) Open the bottom louver. Pull the Burner ON/OFF control box from inside the bo

Page 36

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace41INSTALLATIONFULL SCREEN DOORS1) Before beginning the installation, remove the Glass Door fr

Page 37

42Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATION6) Place the Bottom Frame near the hinges, and fl ip down the hinges from the Bot

Page 38

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace43INSTALLATIONContemporary Faceplate Derating Kit Contains:Qty. Part # Description1 904-434

Page 39

44Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONCONTROL MOUNTING PLATE INSTALLATION(FOR P33-4 UNIT WITH FACEPLATE ONLY)1) Remove

Page 40

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace45INSTALLATION1) Install the control shield with 2 #8 - 1/2" Phillips screws to the botto

Page 41

46Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONDiagram 7Diagram 8Diagram 9Image of P33-4 with Faceplate Image of P33S with Fac

Page 42

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace47INSTALLATIONOptional WALL SWITCH1) Run the supplied 15' of wire through the right or le

Page 43

48Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONWIRING DIAGRAMS This heater does not require a 120V A.C. supply for operation. In

Page 44

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace49INSTALLATIONCaution: Ensure that the wires do not touch any hot surfaces and are away from sh

Page 45

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace5SAFETY LABELSAFETY LABELThis is a copy of the label that accompanies each P33-4 Zero Clearance

Page 46

50Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONINSTALLING THE OPTIONAL FAN120 Volt AC power is needed for the fan switch and blo

Page 47

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace5151OPERATING INSTRUCTIONSCOPY OF THE LIGHTING PLATE INSTRUCTIONSOFFa

Page 48

52Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace52OPERATING INSTRUCTIONSAERATION ADJUSTMENTThe air shutter can be adjusted by moving the adju

Page 49

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace53MAINTENANCEMAINTENANCE INSTRUCTIONS1) Always turn off the gas valve before cleaning. For rel

Page 50

54Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceMAINTENANCETHERMOPILE/THERMOCOUPLE1) Open the bottom louvers.2) Loosen the thermocouple or

Page 51 - OPERATING INSTRUCTIONS

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace55MAINTENANCEREMOVING VALVE1) Shut off the gas supply.2) Remove the louvers (and bay door if

Page 52

56Regency® P33-4 Zero Clearance Direct Vent Gas FireplacePARTS LISTMAIN ASSEMBLY Part # Description Part # Description

Page 53 - MAINTENANCE

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace57PARTS LIST10DOORS & LOUVERS PLEASEREFER SEPARATE SECTIONBRICK PANEL SET343738FAN SWITCH A

Page 54

58Regency® P33-4 Zero Clearance Direct Vent Gas FireplacePARTS LISTBURNER & LOG ASSEMBLY Part Description 53) 4

Page 55

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace59PARTS LISTFLUSH FRONT & LOUVERS Part # Description Part #

Page 56 - PARTS LIST

6Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceREQUIREMENTS5.08: Modifications to NFPA-54, Chapter 10(2) Revise 10.8.3 by adding the followin

Page 57

60Regency® P33-4 Zero Clearance Direct Vent Gas FireplacePARTS LIST Part # Description 1) 434-516 Faceplate A

Page 58

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace61NOTES

Page 59

62Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceNOTES

Page 60

ireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspecbefore it lea

Page 61

© Copyright 2011, FPI Fireplace Products International Ltd. All rights reserved.Installer: Please complete the following informationDealer Name &

Page 62

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace7INSTALLATIONIMPORTANT MESSAGE SAVE THESE INSTRUCTIONSThe P33-NG4 or P33-LP4 Direct Vent Firep

Page 63

8Regency® P33-4 Zero Clearance Direct Vent Gas FireplaceINSTALLATIONDUCT SYSTEM OPTIONKit #946-556The HeatWave Air Duct Kit increases the effectivene

Page 64 - warranty online

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace9INSTALLATIONUNIT DIMENSIONS WITH CONTEMPORARY FACEPLATE33"(838mm)33"(838mm)23"(